Hs 4020

PIPE SIZE: 8″ to 20″ NPS
MATERIAL: Galvanized or HDG Carbon Steel
INSULATION: High density calcium silicate
TEMP. RANGE: Ambient to 1200 degrees F
LAYERING SY.:See layering charts
SHOE LTH,(L): Standard shoe available in 12″ & 18″ lengths
TO ORDER: Specify pipe size, insulation THK., length HENCE: (hs-4020)-nps-thk.-l
LOADS: All loads on adjacent chart have a safety factor of 5
 

L=12″
L=18″
Insulation Thickness
Pipe
Vertical
Vertical
1”
1-1/2”
2”
size
Load(lbs)
Load(lbs)
W
O.D.
H
W
O.D.
H
W
O.D.
H
8”
715
1430
7-5/8″
11-1/2”
4”
8-5/16″
12-1/2”
4”
8-11/16″
13-1/2”
4”
10”
1782
2673
9″
13-1/2”
4”
9-15/16″
14-3/4”
4”
10-5/8″
15-3/4”
4”
12”
2114
3171
10-5/8″
13-15/16”
4”
11-5/16″
16-3/4”
4”
12″
17-3/4”
4”
14”
2321
3482
11-5/16″
17”
4”
12″
18”
4”
12-3/4″
19”
4”
16”
2653
3979
12-3/4″
19”
4”
13-7/16″
20”
4”
14-1/8″
21”
4”
18”
2984
4476
14-1/8″
21”
4”
14-13/16″
22”
4”
15-5/8″
23”
4”
20”
3316
4974
15-5/8″
23”
4”
16-5/16″
24”
4”
17″
25”
4”

 

L=12″
L=18″
Insulation Thickness
Pipe
Vertical
Vertical
2-1/2”
3”
3-1/2″
4”
size
Load(lbs)
Load(lbs)
W
O.D.
H
W
O.D.
H
W
O.D.
H
W
O.D.
H
8”
715
1430
9-15/16″
14-3/4”
4″
10-5/8″
15-3/4”
6”
11-5/16″
16-3/4″
6″
12″
17-3/4”
6”
10”
1782
2673
11-5/16″
16-3/4”
4″
12″
17-3/4”
6”
12-3/4″
18-3/4″
6″
13-7/16″
19-3/4”
6”
12”
2114
3171
12-11/16″
18-3/4”
4″
13-7/16″
19-3/4”
6”
14-1/8″
20-3/4″
6″
14-13/16″
21-3/4”
6”
14”
2321
3482
13-7/16″
20”
4″
14-1/8″
21”
6”
14-13/16″
22″
6″
15-5/8″
23”
6”
16”
2653
3979
14-13/16″
22”
6”
15-5/8″
23”
6”
16-1/4″
24″
6″
17″
25”
6”
18”
2984
4476
16-5/16″
24”
6”
17″
25”
6”
17-11/16″
26″
6″
18-7/16″
27”
6”
20”
3316
4974
17-3/4″
26”
6”
18-7/16″
27”
6”
19-1/8″
28″
6″
19-13/16″
29”
6”
Top