Hs 3030

PIPE SIZE: 24″ to 42″ NPS
MATERIAL: Galvanized or Carbon Steel
INSULATION: High density calcium silicate
TEMP. RANGE: Ambient to 1200 degrees F
LAYERING SY.:See layering charts
SHOE LTH,(L): Standard shoe available in 12″ & 18″ lengths
TO ORDER: Specify pipe size, insulation THK., length HENCE: (hs-3030)-nps-thk.-l
LOADS: All loads on adjacent chart have a safety factor of 5

L=12″
L=18″
Insulation Thickness
Pipe
Vertical
Vertical
1”
1-1/2″
2”
2-1/2″
size
Load(lbs)
Load(lbs)
W
O.D.
H
W
O.D.
H
W
O.D.
H
W
O.D.
H
24”
5969
7958
12”
27”
4”
12”
28”
4”
13”
29”
6”
13”
30”
6”
26”
6466
8621
14”
29-1/2”
4”
14”
30-1/2”
6”
15”
31-1/2”
6”
15-1/2”
32-1/2”
6”
28”
6963
9284
14-1/2”
31-1/2”
4”
15”
32-1/2”
6”
15-1/2”
33-1/2”
6”
16”
34-1/2”
6”
30”
7461
9948
16”
33-1/2”
4”
16-1/2”
34-1/2”
6”
18”
35-1/2”
6”
18”
36-1/2”
6”
32”
7958
10611
18”
35-1/2”
4”
18-1/2”
36-1/2”
6”
18-1/2”
37-1/2”
6”
19”
38-1/2”
6”
34”
8455
11274
18”
37-1/2”
4”
18-1/2”
38-1/2”
6”
19”
39-1/2”
6”
20”
40-1/2”
6”
36”
8953
11937
19”
39-1/2”
4”
19”
40-1/2”
6”
19-1/2”
41-1/2”
6”
19-1/2”
42-1/2”
6”
40”
9948
13263
18”
43-1/2”
4”
18”
44-1/2”
6”
19”
45-1/2”
6”
20”
46-1/2”
6”
42”
10445
13927
18”
45-1/2”
4”
19”
46-1/2”
6”
20”
47-1/2”
6”
21”
48-1/2”
6”

 

L=12″
L=18″
Insulation Thickness
Pipe
Vertical
Vertical
3″
3-1/2″
4″
size
Load(lbs)
Load(lbs)
W
O.D.
H
W
O.D.
H
W
O.D.
H
24”
5969
7958
14”
31”
6”
16″
32″
6″
16”
33”
8”
26”
6466
8621
16”
33-1/2”
6”
16″
34-1/2″
6″
16”
35-1/2”
8”
28”
6963
9284
16”
35-1/2”
6”
17″
36-1/2″
6″
16-1/2”
37-1/2”
8”
30”
7461
9948
20”
37-1/2”
6”
20”
38-1/2″
6″
20”
39-1/2”
8”
32”
7958
10611
20”
39-1/2”
6”
21″
40-1/2″
6″
21”
41-1/2”
8”
34”
8455
11274
21-1/2”
41-1/2”
6”
22″
42-1/2″
6″
21-1/2”
43-1/2”
8”
36”
8953
11937
20”
43-1/2”
6”
21″
44-1/2″
6″
21”
45-1/2”
8”
40”
9948
13263
21”
47-1/2”
6”
22″
48-1/2″
6″
22”
49-1/2”
8”
42”
10445
13927
22”
49-1/2”
6”
23″
50-1/2″
6″
23”
51-1/2”
8”
Top