Graphite Slide Plates

Graphite slide plates can be used in place of PTFE, 25% glass filled slide plates for higher temperature applications. Pure Graphite Slide Plates are recommended for those systems which produce exceptional pressure and heat. With a range of up to 1,000 degrees Fahrenheit for ambient conditions and 3,000 degrees Fahrenheit for inert settings, graphite slide plates can also handle up to 2000 PSI.

Types & Sizes

Technical Information

Installation & Maintenance

Prior to Welding: Locate the slide plate base in the appropriate position on the existing steel surface. Place a protective covering on the graphite. Where seal welding is not required, follow the diagram shown which indicates 1/8” thick fillet weld, 1” long every 4” around entire perimeter of the base. For welding, use GMAW 0.035 wire or SMAW 3/32″ stick.

Where full seal welding is required, use a similar pattern of welding until a full weld is obtained. This method will prevent damage to the graphite. (A full weld will help prevent seepage of water between the slide bearing plate and the support structure.) Avoid overheating, which may destroy the bonding of the graphite to the base plate.

Installation in Concrete: Secure the top and bottom elements together with paper adhesive tape. Then attach the bottom element anchor bolts with wire to the form. After the bottom pour is made, repeat on top element. During the first expansive cycle, the tape will break.

Slide Plate Installation and Maintenance Guide

Request a quote



Acid Plants
Bioenergy Plant
Chemical Plant
Clean Fuels

Cogeneration Plant
Cold / Cryogenc Service
Commercial
Electric Plant

Energy Facility
Ethylene Plant
LLDPE Chemical Plant
LNG Plant

MTBE Plant
Natural Gas Combined Cycle Facility
Natural Gas Processing & Separation
See All

See All Images

The purpose of slide plates is to produce a low-coefficient of friction between a stationary support element and the moving ...Continue Reading

In the majority of cases, bond between the material and its backing plate would become degraded in the presence of ...Continue Reading

The bolted design graphite slide plates can be used in temperatures up to 1,000°F normal atmospheric conditions.

Graphite material is recommended for temperatures higher than 400 degrees F for slide plates. Graphite Slide Plates


More FAQs…

General Dimensions & Specifications

Download Graphite Slide Plate General PDF

Graphite Slide Plates Diagram

Graphite2          

The graphite plates come in two different configurations, the ‘bonded’ and ‘bolted’ assembly. The bonded configuration consists of a ¼” thick graphite pad bonded to a metal backing plate. The bolted configuration consists of a ½” thick graphite pad bonded and bolted to a metallic backing pad. Both configurations can either be tack welded or fully welded to support components.

ASSEMBLY:
Standard Assembly: 2 units of Graphite bonded to 1/4″ carbon steel. For field tack welding. 1/4″ lip. Loads to 2000 PSI, Temperature: +1000° F air, +3,000° inert
Full Weld Assembly: 2 units of Graphite bonded to indicated backing material with 1/2″ lip all around for full welding. Load to 2000 PSI, Temperature: +1000° F air, +3000° F inert

PART # — PTP — Graphite (1/2″ or 1/4″) — 10 Ga. SS — 1/4″ LIP AND SIZE

ADVANTAGES:

• High operating temperature.
• Ease of installation.
• No setting problems.
• Low coefficient of friction.
• No surface treatments, grouting, or expensive mechanical attachment necessary.
• Chemically inert.
• Unaffected by weather conditions.
• Ability to absorb dirt and grit within itself.
• Self-aligning when used in conjunction with elastomeric backing pads.

ORDERING:
1. Please specify the dimensions of the upper plate and dimensions of the lower plate. It is common practice that the upper plate is generally larger than the lower plate.
2. Specify lip dimension (if different than the standard 1/2″).
3. Specify base plate thickness (if different than standard 1/4″).
4. Bolting upper plate is recommended at temperatures above 200°F.

APPLICATIONS:
Bridges: Highway bridges, overpasses, railroad bridges.
Architectural in Wood, Concrete or Steel: Cross beam and girder slip joints, roof slabs and cor-bels, vibration pads, airport hangar doors, domes.
Industrial: Heat exchangers, dust collectors, heavy machinery, refinery equipment, wind tunnels, penstocks, vessels, pipelines, air preheaters, atomic energy applications, transmission towers, storage tanks, offshore drilling rigs.

Download Graphite Slide Plate Specification PDF

Graphite Specification

Property (Room Temperature)UnitsAverageUnits (metric)Average
Bulk Densitylbs./ft.399.26Mg/m31.59
Specific Resistance
With Grain
Across Grain
10-4  ohm-in.


3.33
4.74
ohm-meter


8.47
12.05
Flexural Strength
With Grain
Across Grain
PSI1297
995
kPa
(kN/m2 )
8940
6860
Tensile Strength
With Grain
Across Grain
PSI713
630
kPa
(kN/m2)
4920
4340
Young's Modulus
With Grain
Across Grain
106  PSI0.96
0.61
MPa
(MN/m2)
19840
19320
Coefficient of Thermal Expansion
With Grain
Across Grain
10-6 / °F0.72
1.35
10-6 / °C1.32
2.43
Thermal Conductivity
With Grain
Across Grain
  BTU x ft.
hr. x ft.2 x °F
88
62
W/m x °C152
107
Permeability
With Grain
Across Grain
Darcy's0.493
0.444
Coefficient of Friction0.150.15



Top