Insulated Supports (Figures 4500 – 4800)

Insulated pipe supports are designed to prevent direct heat transfer between pipes and their supports. Thus, they reduce heat loss due to conduction at each support. They serve the following purposes: Carry the load and allow necessary movement at each suppose point, provide insulation in the support area where the regular pipe insulation cannot be installed and minimize the cost of field installation by reducing installation time. The supports are not welded to the pipe and each unit is shipped completely assembled (except for the riser supports and anchor supports, both of which require some welding).

Acid Plants
Ammonia Plant
Chemical Plant
Clean Fuels

Cogeneration Plant
Cold / Cryogenc Service
Commercial
Electric Plant

Energy Facility
Ethylene Plant
Heat Recovery Steam Generation Plant
Hospital

LLDPE Chemical Plant
LNG Plant
MTBE Plant
See All

See More Images 

General Dimensions & Specifications

Download PDF

Fig. 4500: Insulated Shoe Support for Hot Pipe (Hot Shoe)

Fig. 4500: Insulated Shoe Support for Hot Pipe (Hot Shoe)
MATERIAL: Shield and jacket – Galvanized carbon steel.
INSULATION: Asbestos free calcium silicate and/or high-density calcium silicate.
BONDING: Insulation, galvanized jacket and shield can be bonded per customer specifications.
OPTIONS: Support design can be modified for length, insulation thickness, higher load and axial movement. Slide plates are available upon request. Please specify by “-SL” after figure number.
HOW TO ORDER: Specify figure number, pipe size, description, insulation, thickness, and slide plate material, if desired.

PIPE
SIZE
H (in.)L (in.)AXIAL MVMT. (in.)LOAD
CAPACITY (lb.)
APPROX.
WEIGHT (lb.)
3412435039
4412437550
6412467577
8412490099
1041241100108
1241241325122
1441241500127
1641241700137
1841241875191
2041242075205
2441242500232

“H” dimension given above is based on 2″ insulation thickness. Please mention in your inquiry if it is different than listed above. Contact us for your requirements other than those listed above.

Download PDF

Fig. 4600: Insulated Shoe Support for Cold Pipe (Cold Shoes)

Fig. 4600: Insulated Shoe Support for Cold Pipe (Cold Shoes)
MATERIAL: Shield and jacket – Galvanized carbon steel.
INSULATION: High density Polyurethane (PUF)
BONDING: Galvanized jacket, vapor barrier and polyurethane insulation can be bonded per customer specifications.
COATING: Inside surface of polyurethane insulation is covered with pressure sensitive tape and exposed surfaces are coated with monolar mastic.
OPTIONS: Support design can be modified for length, insulation thickness, higher load capacity, and axial movement. Slide plates are also available upon request. Please specify by “-SL” after figure number.
HOW TO ORDER: Specify figure number, pipe size, description, insulation, thickness, and slide plate material, if desired.

PIPE
SIZE
H (in.)L (in.)AXIAL MVMT. (in.)LOAD
CAPACITY (lb.)
APPROX.
WEIGHT (lb.)
3412432038
4412461044
6412490075
841241490100
1041241850108
1241242200123
1441245900132
1641246700143
1841247500197
2041248400212
24412410100240

“H” dimension given above is based on 2″ insulation thickness. Please mention in your inquiry if it is different than listed above. Contact us for your requirements other than those listed above.

Download PDF

Fig. 4700: Clamped Shoe for Insulated Cold Lines

Fig. 4700: Clamped Shoe for Insulated Cold Lines
MATERIAL: Clamps and base – stainless steel. Base plate – carbon steel.
INSULATION: Micarta® or Permali®
OPTIONS: Support design can be modified for length, insulation thickness and axial movement. Slide plates and guides are also available upon request.
HOW TO ORDER: Specify figure number, pipe size and insulation thickness. Also specify any special dimensions.

PIPE SIZE H (in.)L (in.)Axial
Movement (in.)
Vertical
Load (lb.)
APPROX.
WEIGHT (lb.)
3
6
12
4
4000
34
4
6
12
4
5000
35
6
6
12
4
6000
52
8
6
12
4
6000
60
10
6
12
4
8000
93
12
6
12
4
8000
136
14
6
12
4
8000
164
16
6
12
4
12000
183
18
8
12
4
12000
352
20
8
12
4
15000
415
24
8
12
4
15000
538

Contact us for your requirements other than those listed above.

Download PDF

Fig. 4800-A: Insulated Cold Shoe with G10 (Anchor)

Fig 4800 a
SIZE RANGE: 2″ thru 54″
MATERIAL: Shoe: Same as pipe material / Bottom plate: carbon steel
INSULATION: G10
OPTIONS: Support design can be modified for length, insulation thickness and axial movement. Slide plates are provided depending on pipe movement
HOW TO ORDER: Specify figure number, pipe size, description.

PIPE SIZESHOE LENGTH (L)SHOE HEIGHT (H)AXIAL LOAD (Lbs)LATERAL LOAD (Lbs)COMPRESSION LOAD (Lbs)AXIAL MOVEMENT (In)
21267,0002,37120,2074
31267,0002,37120,2074
41267,0002,37120,2074
61267,0002,37120,2074
812611,00010,00021,3304
1012611,00010,00021,3304
1212611,00011,00050,5164
1412611,00011,00050,5164
1612611,00011,00050,5174
1812611,00011,00050,5174
2012611,00011,00050,5174
2418611,00011,00060,6244
3018644,00044,000132,6024
3624645,00045,000176,3904
4024645,00046,000251,4644
4224645,00046,000251,4644
4824645,00046,000269,4264
5424645,50046,000287,3874

Download PDF

Fig. 4800-G: Insulated Cold Shoe with G10 (Guides)

Fig 4800 g
SIZE RANGE: 2″ thru 54″
MATERIAL: Shoe: Same as pipe material / Bottom plate: carbon steel
INSULATION: G10
OPTIONS: Support design can be modified for length, insulation thickness and axial movement. Slide plates are provided depending on pipe movement
HOW TO ORDER: Specify figure number, pipe size, description.

PIPE SIZESHOE LENGTH (L)SHOE HEIGHT (H)AXIAL LOAD (Lbs)LATERAL LOAD (Lbs)COMPRESSION LOAD (Lbs)AXIAL MOVEMENT (In)
21267,0002,37120,2074
31267,0002,37120,2074
41267,0002,37120,2074
61267,0002,37120,2074
812611,00010,00021,3304
1012611,00010,00021,3304
1212611,00011,00050,5164
1412611,00011,00050,5164
1612611,00011,00050,5174
1812611,00011,00050,5174
2012611,00011,00050,5174
2418611,00011,00060,6244
3018644,00044,000132,6024
3624645,00045,000176,3904
4024645,00046,000251,4644
4224645,00046,000251,4644
4824645,00046,000269,4264
5424645,50046,000287,3874

Download PDF

Fig. 4800-S: Insulated Cold Shoe with G10 (Slides)

Fig 4800 s
SIZE RANGE: 2″ thru 54″
MATERIAL: Shoe: Same as pipe material / Bottom plate: carbon steel
INSULATION: G10
OPTIONS: Support design can be modified for length, insulation thickness and axial movement. Slide plates are provided depending on pipe movement
HOW TO ORDER: Specify figure number, pipe size, description.

PIPE SIZESHOE LENGTH (L)SHOE HEIGHT (H)AXIAL LOAD (Lbs)LATERAL LOAD (Lbs)COMPRESSION LOAD (Lbs)AXIAL MOVEMENT (In)
21267,0002,37120,2074
31267,0002,37120,2074
41267,0002,37120,2074
61267,0002,37120,2074
812611,00010,00021,3304
1012611,00010,00021,3304
1212611,00011,00050,5164
1412611,00011,00050,5164
1612611,00011,00050,5174
1812611,00011,00050,5174
2012611,00011,00050,5174
2418611,00011,00060,6244
3018644,00044,000132,6024
3624645,00045,000176,3904
4024645,00046,000251,4644
4224645,00046,000251,4644
4824645,00046,000269,4264
5424645,50046,000287,3874

Size Range: For use with 1/2″ through 72″, most designs. insulation thickness of 1″. 1-1/2″, 2″, 2-1/2″, 3″, 3-1/2″, 4″ and larger sizes where specified.

How to Size: Refer to “Insulation Chart” below for Sizing the Insulation Material.

Ordering: Specify figure number, pipe size, insulation thickness, and insulating material

Example:
Fig. 4700-4-3-B
• 4700 = Type of Insulated Shoe (cold)
• 4 = Nominal Pipe Size
• 3= Insulation Thickness
• B = Insulation Material (Micarta)

NOMINAL INSULATION THICKNESS (in.)INSULATION O.D. (in.)APPROX. INSULATION THICKNESS (in.)

Pipe size: 1/2" (O.840 O.D.)

12 7/81
1 1/241 9/16
252 1/16
2 1/26 5/82 7/8
37 5/83 3/8
3 1/28 5/83 7/8
49 5/84 3/8

Pipe size: 3/4" (1.050 O.D.)

12 7/87/8
1 1/241 7/16
251 15/16
2 1/26 5/82 3/4
37 5/83 1/4
3 1/28 5/83 3/4
49 5/84 1/4

Pipe size: 1" (1.315 O.D.)

13 1/21 1/16
1 1/24 1/21 9/16
25 9/162 1/8
2 1/26 5/82 5/8
37 5/83 1/8
3 1/28 5/83 5/8
49 5/84 1/8

Pipe size: 1 1/4" (1.66 O.D.)

13 1/215/16
1 1/251 11/16
25 9/161 15/16
2 1/26 5/82 1/2
37 5/83
3 1/28 5/83 1/2
49 5/84

Pipe size: 1 1/2" (1.90 O.D.)

141 1/16
1 1/251 9/16
26 5/82 3/8
2 1/27 5/82 7/8
38 5/83 3/8
3 1/29 5/83 7/8
410 3/44 7/16

Pipe size: 2" (2 3/8" O.D.)

14 1/21 1/16
1 1/25 9/161 9/16
26 5/82 1/8
2 1/27 5/82 5/8
38 5/83 1/8
3 1/29 5/83 5/8
410 3/44 3/16

Pipe size: 2 1/2" (2 7/8" O.D.)

151 1/16
1 1/26 5/81 7/8
27 5/82 3/8
2 1/28 5/82 7/8
39 5/83 3/8
3 1/210 3/43 15/16
411 3/44 7/16

Pipe size: 3" (3 1/2" O.D.)

15 9/161
1 1/26 5/81 9/16
27 5/82 1/16
2 1/28 5/82 9/16
39 5/83 1/16
3 1/210 3/43 5/8
411 3/44 1/8

Pipe size: 3 1/2" (4" O.D.)

16 5/81 5/16
1 1/27 5/81 13/16
28 5/82 5/16
2 1/29 5/82 13/16
310 3/43 3/8
3 1/211 3/43 7/8
412 3/44 3/8

Pipe size: 4" (4 1/2" O.D.)

16 5/81 1/16
1 1/27 5/81 9/16
28 5/82 1/16
2 1/29 5/82 9/16
310 3/43 1/8
3 1/211 3/43 5/8
412 3/44 1/8

Pipe size: 4 1/2" (5" O.D.)

17 5/81 5/16
1 1/28 5/81 13/16
29 5/82 5/16
2 1/210 3/42 7/8
311 3/43 3/8
3 1/212 3/43 7/8
4144 1/2

Pipe size: 5" (5 9/16" O.D.)

17 5/81
1 1/28 5/81 1/2
29 5/82
2 1/210 3/42 9/16
311 3/43 1/16
3 1/212 3/43 9/16
4144 3/16

Pipe size: 6" (6 5/8" O.D.)

18 5/815/16
1 1/29 5/81 7/16
210 3/42
2 1/211 3/42 1/2
312 3/43
3 1/2143 5/8
4154 1/8

Pipe size: 7" (7 5/8" O.D.)

19 5/81
1 1/210 3/41 1/2
211 3/42
2 1/212 3/42 1/2
3143 1/8
3 1/2153 5/8
4164 1/8

Pipe size: 8" (8 5/8" O.D.)

110 3/41 1/16
1 1/211 3/41 1/2
212 3/42
2 1/2142 5/8
3153 1/8
3 1/2163 5/8
4174 1/8

Pipe size: 9" (9 5/8" O.D.)

111 3/41 1/16
1 1/212 3/41 1/2
2142
2 1/2152 5/8
3163 1/8
3 1/2173 5/8
4184 1/8

Pipe size: 10" (10 3/4" O.D.)

112 3/41
1 1/2141 9/16
2152 1/16
2 1/2162 9/16
3173 1/16
3 1/2183 9/16
4194 1/16

Pipe size: 11" (11 3/4" O.D.)

1141 1/8
1 1/2151 9/16
2162 1/16
2 1/2172 9/16
3183 1/16
3 1/2193 9/16
4204 1/16

Pipe size: 12" (12 3/4" O.D.)

1151 1/8
1 1/2161 9/16
2172 1/16
2 1/2182 9/16
3193 1/16
3 1/2203 9/16
4214 1/16

Pipe size: 14" (14" O.D.)

1162
1 1/2171 7/16
2181 15/16
2 1/2192 7/16
3202 15/16
3 1/2213 7/16
4223 15/16
Large sizes, insulation O.D. are in 1" increments.

Insulation thicknesses through 36" same as nominal.

All dimensions rounded to the nearest 1/16".

 



Top